CyberRota Analysis
This is a critical severity vulnerability with a CVSS score of 9.8. Public exploit code or proof-of-concept references have been detected in its references. Its EPSS score suggests a 13.4% probability of exploitation in the next 30 days. It may be remotely exploitable.
Public Exploit Signal
A public exploit, PoC, GitHub repository or Metasploit reference was detected for this CVE.
Note: these links are listed for security research and verification purposes only.
Original NVD Description
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Related CVEs
Other vulnerabilities affecting the same vendor(s)