CyberRota Analysis
This is a critical severity vulnerability with a CVSS score of 9.8. It is listed in CISA's Known Exploited Vulnerabilities catalog, indicating confirmed active exploitation in the wild. Its EPSS score suggests a 61.0% probability of exploitation in the next 30 days. Exploitation may require the attacker to be authenticated.
CISA KEV Details
Status: This CVE is listed in CISA's Known Exploited Vulnerabilities catalog.
Ransomware use: Unknown
Added to KEV: 2026-03-05
Required action: Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.
Original NVD Description
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
Related CVEs